Technical data
Powador 10.0 TL3 | 12.0 TL3 | 14.0 TL3 | 18.0 TL3
Electrical data 10.0 TL3 12.0 TL3
Input variables
Max. recommended PV generator power 10 000 W 12 000 W
MPP range 200 V ... 800 V* 200 V ... 800 V*
Starting voltage 250 V 250 V
No-load voltage 1 000 V 1 000 V
Max. input current 2 x 18.6 A 2 x 18.6 A
Number of MPP trackers 2 2
Max. power/tracker 9,2 kW 10,2 kW
Number of strings 2 x 2 2 x 2
Output variables
Rated output 9 000 VA 10 000 VA
Supply voltage acc. to local requirements acc. to local requirements
Rated current 3 x 13.0 A 3 x 14.5 A
Rated frequency 50 Hz / 60 Hz 50 Hz / 60 Hz
cos phi 0.80 inductive ... 0.80 capacitive 0.80 inductive ... 0.80 capacitive
Number of grid phases 3 3
General electrical data
Max. effi ciency 98.0 % 98.0 %
Europ. effi ciency 97.4 % 97.5 %
Night consumption 1,5 W 1,5 W
Switching plan transformerless transformerless
Grid monitoring acc. to local requirements acc. to local requirements
Mechanical data
Display graphical display + LEDs graphical display + LEDs
Control units 4-way navigation + 2 buttons 4-way navigation + 2 buttons
Interfaces Ethernet, USB, RS485, S0 output Ethernet, USB, RS485, S0 output
Fault signalling relay potential-free NOC max. 230 V / 1 A potential-free NOC max. 230 V / 1 A
Connections DC: solar connector, AC: cable connection
M40 and terminal
DC: solar connector, AC: cable connection
M40 and terminal
Ambient temperature -25 °C … +60 °C*** -25 °C … +60 °C***
Cooling temperature-dependent fan temperature-dependent fan
Protection class IP65 IP65
Noise emission < 45 dB (A) (noiseless when operated without
fan)
< 45 dB (A) (noiseless when operated without
fan)
DC switch integrated integrated
Casing aluminium casting aluminium casting
H x W x D 690 x 420 x 200 mm 690 x 420 x 200 mm
Weight 40 kg 40 kg
* The possible input power is reduced at voltages lower than 350V. The input current is limited to 18.6A per input. / ** The possible input power is reduced at voltages lower than 420V.
The input current is limited to 18.6A per input. *** Power derating at high ambient temperatures. /
Conforms to the country-specifi c standards and regulations according to the country version that has been set.
Electrical data 14.0 TL3 18.0 TL3
Input variables
Max. recommended PV generator power 14 000 W 18 000 W
MPP range 200 V ... 800 V* 200 V ... 800 V**
Starting voltage 250 V 250 V
No-load voltage 1 000 V 1 000 V
Max. input current 2 x 18.6 A 2 x 18.6 A
Number of MPP trackers 2 2
Max. power/tracker 12,8 kW 12,8 kW
Number of strings 2 x 2 2 x 2
Output variables
Rated output 12 500 VA 15 000 VA
Supply voltage acc. to local requirements acc. to local requirements
Rated current 3 x 18.1 A 3 x 21.7 A
Rated frequency 50 Hz / 60 Hz 50 Hz / 60 Hz
cos phi 0.80 inductive ... 0.80 capacitive 0.80 inductive ... 0.80 capacitive
Number of grid phases 3 3
General electrical data
Max. effi ciency 98.0 % 98.0 %
Europ. effi ciency 97.6 % 97.6 %
Night consumption 1,5 W 1,5 W
Switching plan transformerless transformerless
Grid monitoring acc. to local requirements acc. to local requirements
Mechanical data
Display graphical display + LEDs graphical display + LEDs
Control units 4-way navigation + 2 buttons 4-way navigation + 2 buttons
Interfaces Ethernet, USB, RS485, S0 output Ethernet, USB, RS485, S0 output
Fault signalling relay potential-free NOC max. 230 V / 1 A potential-free NOC max. 230 V / 1 A
Connections DC: solar connector, AC: cable connection
M40 and terminal
DC: solar connector, AC: cable connection
M40 and terminal
Ambient temperature -25 °C … +60 °C*** -25 °C … +60 °C***
Cooling temperature-dependent fan temperature-dependent fan
Protection class IP65 IP65
Noise emission < 45 dB (A) (noiseless when operated without
fan)
< 45 dB (A) (noiseless when operated without
fan)
DC switch integrated integrated
Casing aluminium casting aluminium casting
H x W x D 690 x 420 x 200 mm 690 x 420 x 200 mm
Weight 40 kg 40 kg
NEW
* The possible input power is reduced at voltages lower than 350V. The input current is limited to 18.6A per input. / ** The possible input power is reduced at voltages lower than 420V.
The input current is limited to 18.6A per input. *** Power derating at high ambient temperatures. /
Conforms to the country-specifi c standards and regulations according to the country version that has been set.